LIT1368E Flex Training Manual
Page | 26
32600 LIT1368F
An IP address and port number have to be added. Additionally the Persistent or the UDP protocol
for the device must be set.
Persistent, if selected, has a timeout set to 1 minute. This is here to allow the user to set the
connection timeout of any misbehaving Ethernet devices. The default setting should remain as is
unless instructed to change it by FSR Customer support or the manufacturer of the device you are
trying to control.
TCP or Transmission Control Protocol and UDP or User Datagram Protocol: TCP is the default
protocol however; UDP may be selected for devices requiring such connectivity. When UDP is
selected, the persistent setting is automatically turned off.